DNG DC Inverter Series
SEPTEMBER – 2008
Indoor Units Outdoor Units
DNG 50 DCI DCI 50
DNG 60 DCI DCI 60
DNG 72 DCI DCI 72
DNG 80 DCI DCI 80
DNG 100 DCI OU12 4HP DCI
DNG 125 DCI OU12 5HP DCI
REFRIGERANT
R410A
HEAT PUMP
SM DNGDCI 2-E.1 GB
CONTENT
Vista de página 0
1 2 3 4 5 6 ... 117 118

Resumo do Conteúdo

Página 1 - DNG DC Inverter Series

DNG DC Inverter SeriesSEPTEMBER – 2008Indoor Units Outdoor UnitsDNG 50 DCI DCI 50DNG 60 DCI DCI 60DNG 72 DCI DCI 72DNG 80 DCI DCI 80DNG 100 DCI OU12

Página 2 - Photos are not contractual

2-3PRODUCT DATA SHEETSM DNGDCI 2-E.1 GB2.3 DNG72 DCI Model Indoor Unit DNG 72 DCIModel Outdoor Unit DCI 72 R410AInstallation Method of Pipe FlaredChar

Página 3 - Table of Contents

13-15TROUBLESHOOTINGSM DNGDCI 2-E.1 GB13.2.4.1 Indoor unit diagnostics and corrective actionsNo.Fault Probable Cause Corrective Action1-4 Sensor fail

Página 4 - 1. INTRODUCTION

13-16TROUBLESHOOTING SM DNGDCI 2-E.1 GB 13.2.5.4 Checking the Outdoor Fan MotorCheck FAN-Power and FAN-Halls connections - Repair if needed.Rotate th

Página 5 - INTRODUCTION

13-17TROUBLESHOOTINGSM DNGDCI 2-E.1 GB13.2.5.10 Checking for electromagnetic interferance (EMC problems)EMC troubles to the A/C unitLocations most su

Página 6

13-18TROUBLESHOOTING SM DNGDCI 2-E.1 GB 13.2.6.3 Advise: Open the Outdoor unit controller cover only after one minute from power off. Measure the el

Página 7 - 1.11.1 R410A

14-1EXPLODED VIEWS AND SPARE PARTS LISTSSM DNGDCI 2-E.1 GB14. EXPLODED VIEWS AND SPARE PARTS LISTS14.1 Indoor Unit: DNG 50/60/72/80/100/125CONTENT

Página 8 - 2. PRODUCT DATA SHEET

14-2EXPLODED VIEWS AND SPARE PARTS LISTSSM DNGDCI 2-E.1 GB14.2 Indoor Unit: DNG 50/60 DCI14.3 Indoor Unit: DNG 72 DCINo. Part No. Description Qty1

Página 9 - 2.2 DNG60 DCI

14-3EXPLODED VIEWS AND SPARE PARTS LISTSSM DNGDCI 2-E.1 GB14.4 Indoor Unit: DNG 80 DCINo. Part No. Description Qty1 473419 IU COIL GR/HDR 1 2 473

Página 10 - 2.3 DNG72 DCI

14-4EXPLODED VIEWS AND SPARE PARTS LISTSSM DNGDCI 2-E.1 GB14.9 Outdoor Unit: DCI 50CONTENT

Página 11 - 2.4 DNG80 DCI

14-5EXPLODED VIEWS AND SPARE PARTS LISTSSM DNGDCI 2-E.1 GB14.10 Outdoor Unit: DCI 50No. Part No. Description Unit1 433218 Front panel A 12 4526340

Página 12 - 2.5 DNG100 DCI

14-6EXPLODED VIEWS AND SPARE PARTS LISTSSM DNGDCI 2-E.1 GB14.5 Outdoor Unit: DCI 60CONTENT

Página 13 - 2.6 DNG125 DCI

2-4PRODUCT DATA SHEETSM DNGDCI 2-E.1 GB2.4 DNG80 DCI Model Indoor Unit DNG 80 DCIModel Outdoor Unit DCI 80 R410AInstallation Method of Pipe FlaredChar

Página 14 - 3. RATING CONDITIONS

14-7EXPLODED VIEWS AND SPARE PARTS LISTSSM DNGDCI 2-E.1 GB14.6 Outdoor Unit: DCI 6012 3DUW12 '(6&5,7,21 XQLW1 4517144 FAN COVER PP+

Página 15 - 4. OUTLINE DIMENSIONS

14-8EXPLODED VIEWS AND SPARE PARTS LISTSSM DNGDCI 2-E.1 GB14.7 Outdoor Unit: DCI 72/80CONTENT

Página 16 - Outdoor Unit: DCI 60

14-9EXPLODED VIEWS AND SPARE PARTS LISTSSM DNGDCI 2-E.1 GB14.8 Outdoor Unit: DCI 72/80No. Part No. Description Unit 1 465100000 Outlet grid 1 2 4

Página 17 - 4.4 Outdoor Unit: DCI 72/80

14-10EXPLODED VIEWS AND SPARE PARTS LISTSSM DNGDCI 2-E.1 GB14.11 Outdoor Unit: OU12 4-5HP DCICONTENT

Página 18 - 5.1 DNG50 DCI

14-11EXPLODED VIEWS AND SPARE PARTS LISTSSM DNGDCI 2-E.1 GB14.12 Outdoor Unit: OU12 4-5HP DCI147043694215221637CONTENT

Página 19 - 5.1.3 Heating

14-12EXPLODED VIEWS AND SPARE PARTS LISTSSM DNGDCI 2-E.1 GB14.13 Outdoor Unit: OU12 4-5HP DCICONTENT

Página 20 - (Cooling – Test Mode)

14-13EXPLODED VIEWS AND SPARE PARTS LISTSSM DNGDCI 2-E.1 GB14.14 Outdoor Unit: OU12 4HP DCISP No. Item Description Rev Qty1 437045 UPPER COVER EL13 O

Página 21 - (Heating – Test Mode)

14-14EXPLODED VIEWS AND SPARE PARTS LISTSSM DNGDCI 2-E.1 GB14.15 Outdoor Unit: OU12 5HP DCISP No. Item Description Rev Qty1 437045 UPPER COVER EL13 O

Página 22 - Capacity Ratio

15-1APPENDIX ASM DNGDCI 2-E.1 GBAPPENDIX AINSTALLATION AND OPERATION MANUAL► INSTALLATION AND OPERATION MANUAL: DNG 50/60/72/80/100/125 DCICONTENT

Página 23 - 5.2 DNG60 DCI

2-5PRODUCT DATA SHEETSM DNGDCI 2-E.1 GB2.5 DNG100 DCIModel Indoor Unit DNG 100 DCIModel Outdoor Unit OU12 4HP DCIInstallation Method of Pipe FlaredCha

Página 24 - 5.2.3 Heating

2-6PRODUCT DATA SHEETSM DNGDCI 2-E.1 GB2.6 DNG125 DCI Model Indoor Unit DNG 125 DCIModel Outdoor Unit OU12 5HP DCIInstallation Method of Pipe FlaredCh

Página 25

3-1RATING CONDITIONS Revision Y06-01SM DNGDCI 2-E.1 GB3. RATING CONDITIONSStandard conditions in accordance with ISO 5

Página 26

4-1OUTLINE DIMENSIONSSM DNGDCI 2-E.1 GB4. OUTLINE DIMENSIONS4.1 Indoor Unit: DNG 50, 60, 72, 80, 100, 125Model A B C D E F G H I J K LDNG50,60,72,807

Página 27

4-2OUTLINE DIMENSIONSSM DNGDCI 2-E.1 GB4.2 Outdoor Unit: DCI 504.3 Outdoor Unit: DCI 60CONTENT

Página 28 - 5.3 DNG72 DCI

4-3OUTLINE DIMENSIONSSM DNGDCI 2-E.1 GB4.4 Outdoor Unit: DCI 72/804.5 Outdoor Unit: DCI 120/125 (OU12 DCI 4-5HP)CONTENT

Página 29 - 5.3.3 Heating

5-1PERFORMANCE DATA & PRESSURE CURVESSM DNGDCI 2-E.1 GB5. PERFORMANCE DATA & PRESSURE CURVES5.1 DNG50 DCI 5.1.1 Cooling Capacity (kW)ID COIL

Página 30

5-2PERFORMANCE DATA & PRESSURE CURVES SM DNGDCI 2-E.1 GB5.1.3 HeatingID COIL ENTERING AIR DB TEMPERATURE [C0]OD COIL ENTERING AIR DB/WB TEM

Página 31 - Discharge Pressure [kPa]

ALIST OF EFFECTIVE PAGESSM DNGDCI 2-E.1 GBLIST OF EFFECTIVE PAGESNote: Changes in the pages are indicated by a “Revision#” in the footer of each effe

Página 32

5-3PERFORMANCE DATA & PRESSURE CURVESSM DNGDCI 2-E.1 GB5.1.5 Pressure Curves (Cooling – Test Mode) Discharge Pressure VS. Outdoor Temp'.10001

Página 33 - 5.4 DNG 80 DCI

5-4PERFORMANCE DATA & PRESSURE CURVES SM DNGDCI 2-E.1 GB5.1.6 Pressure Curves (Heating – Test Mode)Suction Pressure VS.Outdoor Temp'.2

Página 34 - 5.4.3 Heating

5-5PERFORMANCE DATA & PRESSURE CURVESSM DNGDCI 2-E.1 GB5.1.7 Capacity Correction Factor Due to Tubing Length Cooling Heating0.800.850.900.951.004

Página 35

5-6PERFORMANCE DATA & PRESSURE CURVES SM DNGDCI 2-E.1 GB5.2 DNG60 DCI5.2.1 Cooling Capacity (kW)ID COIL ENTERING AIR DB/WB TEMPERATURE [C0

Página 36

5-7PERFORMANCE DATA & PRESSURE CURVESSM DNGDCI 2-E.1 GB5.2.3 HeatingID COIL ENTERING AIR DB TEMPERATURE [C0]OD COIL ENTERING AIR DB/WB TEMPERATURE

Página 37

5-8PERFORMANCE DATA & PRESSURE CURVES SM DNGDCI 2-E.1 GB5.2.5 Pressure Curves (Cooling – Test Mode)Discharge Pressure VS. Outdoor Temp&apos

Página 38 - 5.5 DNG100 DCI

5-9PERFORMANCE DATA & PRESSURE CURVESSM DNGDCI 2-E.1 GB5.2.6 Pressure Curves (Heating – Test Mode)Suction Pressure VS.Outdoor Temp'.200300400

Página 39 - 5.5.3 Heating

5-10PERFORMANCE DATA & PRESSURE CURVES SM DNGDCI 2-E.1 GB5.2.7 Capacity Correction Factor Due to Tubing Length Cooling Heating0.800.850.90

Página 40 - (Cooling – Technician Mode)

5-11PERFORMANCE DATA & PRESSURE CURVESSM DNGDCI 2-E.1 GB5.3 DNG72 DCI5.3.1 Cooling Capacity (kW)ID COIL ENTERING AIR DB/WB TEMPERATURE [C0]OD COI

Página 41 - (Heating – Technician Mode)

5-12PERFORMANCE DATA & PRESSURE CURVES SM DNGDCI 2-E.1 GB5.3.3 HeatingID COIL ENTERING AIR DB TEMPERATURE [C0]OD COIL ENTERING AIR DB/WB TE

Página 42 - 5.6 DNG125 DCI

iTABLE OF CONTENTSSM DNGDCI 2-E.1 GBTable of Contents1. INTRODUCTION ...

Página 43 - 5.6.3 Heating

5-13PERFORMANCE DATA & PRESSURE CURVESSM DNGDCI 2-E.1 GB5.3.5 Pressure Curves (Cooling – Test Mode)Discharge Pressure VS. Outdoor Temp'.10001

Página 44

5-14PERFORMANCE DATA & PRESSURE CURVES SM DNGDCI 2-E.1 GB5.3.6 Pressure Curves (Heating – Test Mode)Suction Pressure VS.Outdoor Temp'.

Página 45

5-15PERFORMANCE DATA & PRESSURE CURVESSM DNGDCI 2-E.1 GB5.3.7 Capacity Correction Factor Due to Tubing Length Cooling Heating0.750.800.850.900.95

Página 46 - 5.7.2 Heating

5-16PERFORMANCE DATA & PRESSURE CURVES SM DNGDCI 2-E.1 GB5.4 DNG 80 DCI5.4.1 Cooling Capacity (kW)ID COIL ENTERING AIR DB/WB TEMPERATURE [

Página 47 - 5.8.2 Heating

5-17PERFORMANCE DATA & PRESSURE CURVESSM DNGDCI 2-E.1 GB5.4.3 HeatingID COIL ENTERING AIR DB TEMPERATURE [C0]OD COIL ENTERING AIR DB/WB TEMPERATUR

Página 48 - 5.9 Calculation Example

5-18PERFORMANCE DATA & PRESSURE CURVES SM DNGDCI 2-E.1 GBDischarge Pressure VS. Outdoor Temp'.1000125015001750200022502500275030003250

Página 49 - 6. AIRFLOW CURVES

5-19PERFORMANCE DATA & PRESSURE CURVESSM DNGDCI 2-E.1 GBSuction Pressure VS.Outdoor Temp'.2003004005006007008009001000110012001300-15 -10 -5

Página 50 - 6.4 Model: DNG 80 DCI

5-20PERFORMANCE DATA & PRESSURE CURVES SM DNGDCI 2-E.1 GB5.4.7 Capacity Correction Factor Due to Tubing Length Cooling Heating0.750.800.85

Página 51 - 6.6 Model: DNG 125 DCI

5-21PERFORMANCE DATA & PRESSURE CURVESSM DNGDCI 2-E.1 GB5.5 DNG100 DCI 5.5.1 Cooling Capacity (kW) ID COIL ENTERING AIR DB/WB TEMPERATURE [°C]OD

Página 52 - AIRFLOW CURVES

5-22PERFORMANCE DATA & PRESSURE CURVES SM DNGDCI 2-E.1 GB5.5.3 HeatingID COIL ENTERING AIR DB TEMPERATURE [°C]OD COIL ENTERING AIR DB/WB TE

Página 53 - 7.1 Sound Pressure Level

1-1INTRODUCTIONSM DNGDCI 2-E.1 GB1. INTRODUCTION1.1 GeneralThe new DNG DCI INVERTER ducted split unit range comprises the following RC (heat pump) mo

Página 54 - DNG 72 DNG 80

5-23PERFORMANCE DATA & PRESSURE CURVESSM DNGDCI 2-E.1 GB5.5.5 Pressure Curves (Cooling – Technician Mode)Suction Pressure - Cooling (Technician Mo

Página 55 - 7.3 Outdoor units

5-24PERFORMANCE DATA & PRESSURE CURVES SM DNGDCI 2-E.1 GB5.5.6 Pressure Curves (Heating – Technician Mode)Suction Pressure - Heating (Techn

Página 56 - DCI 80 Cooling DCI 80 Heating

5-25PERFORMANCE DATA & PRESSURE CURVESSM DNGDCI 2-E.1 GB5.6 DNG125 DCI5.6.1 Cooling Capacity (kW) ID COIL ENTERING AIR DB/WB TEMPERATURE [°C]OD CO

Página 57 - 8. ELECTRICAL DATA

5-26PERFORMANCE DATA & PRESSURE CURVES SM DNGDCI 2-E.1 GB5.6.3 HeatingID COIL ENTERING AIR DB TEMPERATURE [°C]OD COIL ENTERING AIR DB/WB TE

Página 58 - 9. WIRING DIAGRAMS

5-27PERFORMANCE DATA & PRESSURE CURVESSM DNGDCI 2-E.1 GB5.6.5 Pressure Curves (Cooling – Technician Mode)Suction Pressure - Cooling (Technician Mo

Página 59 - WIRING DIAGRAMS

5-28PERFORMANCE DATA & PRESSURE CURVES SM DNGDCI 2-E.1 GB5.6.6 Pressure Curves (Heating – Technician Mode)Suction Pressure - Heating (Techn

Página 60 - OUTDOOR UNIT CIRCUIT DIAGRAM

5-29PERFORMANCE DATA & PRESSURE CURVESSM DNGDCI 2-E.1 GB5.7 Capacity Correction Factor for Tubing Length5.7.1 Cooling5.7.2 Heating0.750.800.850.9

Página 61 - 9.5 Outdoor Unit: DCI 72/80

5-30PERFORMANCE DATA & PRESSURE CURVES SM DNGDCI 2-E.1 GB5.8 Pressure Correction Factor for Tubing Length5.8.1 Cooling5.8.2 HeatingPressur

Página 62 - 10. REFRIGERATION DIAGRAMS

5-31PERFORMANCE DATA & PRESSURE CURVESSM DNGDCI 2-E.1 GB5.9 Calculation ExampleOutdoor Unit OU12 5HP DCIIndoor Unit DNG 125 DCIOperation Mode Cool

Página 63 - ¼” ⅜” ½” ⅝” ¾”

6-1AIRFLOW CURVESSM DNGDCI 2-E.1 GB6. AIRFLOW CURVES6.1 Model: DNG 50 DCI6.2 Model: DNG 60 DCICONTENT

Página 64 - 12 CONTROL SYSTEM

1-2INTRODUCTIONSM DNGDCI 2-E.1 GB1.3 Indoor Unit The DNG DCI indoor unit is a low silhouette ducted unit, and can be easily fitted to many types of res

Página 65 - CONTROL SYSTEM

6-2AIRFLOW CURVES SM DNGDCI 2-E.1 GB6.3 Model: DNG 72 DCI6.4 Model: DNG 80 DCICONTENT

Página 66

6-3AIRFLOW CURVESSM DNGDCI 2-E.1 GB6.5 Model: DNG 100 DCI6.6 Model: DNG 125 DCIAir Flow vs. External Static Pressure01020304050607080901001101201301

Página 67

6-4AIRFLOW CURVES SM DNGDCI 2-E.1 GB6.7 DNG UNITS RANGE AIR FLOW CORRECTION FACTORS (at nominal rating conditions — Test mode).Air Flow Rate [

Página 68

7-1SOUND LEVEL CHARACTERISTICSSM DNGDCI 2-E.1 GB7. SOUND LEVEL CHARACTERISTICS7.1 Sound Pressure LevelFigure 17.2 Soud Pressure Level Spectrum (Mea

Página 69 - EEVEEVEEV

7-2SOUND LEVEL CHARACTERISTICS SM DNGDCI 2-E.1 GBDNG 72 DNG 80FAN SPEED LINEHIMELOCONTENT

Página 70

7-3SOUND LEVEL CHARACTERISTICSSM DNGDCI 2-E.1 GB7.3 Outdoor units7.4 Sound Pressure Level Spectrum (Measured as Figure 2)DCI 50 Cooling DCI 50 Heatin

Página 71 - 12.9 Protections

7-4SOUND LEVEL CHARACTERISTICS SM DNGDCI 2-E.1 GBDCI 72 Cooling DCI 72 HeatingDCI 80 Cooling DCI 80 HeatingCONTENT

Página 72

8-1ELECTRICAL DATASM DNGDCI 2-E.1 GB8. ELECTRICAL DATA8.1 Single Phase UnitsMODEL DNG50 DNG60 DNG72 DNG80 Power Supply 1 PH ,220-240VAC ,50HZ Con

Página 73

9-1WIRING DIAGRAMSSM DNGDCI 2-E.1 GB9. WIRING DIAGRAMS9.1 Indoor Unit: DNG 50 DCI9.2 Indoor Unit: DNG 60 DCICONTENT

Página 74

9-2WIRING DIAGRAMS SM DNGDCI 2-E.1 GB9.3 Indoor Unit: DNG 72/80 DCICONTENT

Página 75

1-3INTRODUCTIONSM DNGDCI 2-E.1 GB1.7 Outdoor UnitThe DNG DCI INV outdoor units can be installed as floor or wall mounted units by using a wall supporti

Página 76

9-3WIRING DIAGRAMSSM DNGDCI 2-E.1 GB9.4 Outdoor Unit: DCI 50/609.4.1 DCI 50/60 for Indoor Power Supply9.4.2 DCI 50/60 for Outdoor Power SupplyNOTE:

Página 77 - P1 P2 P3 P4

9-4WIRING DIAGRAMS SM DNGDCI 2-E.1 GB9.5 Outdoor Unit: DCI 72/80CONTENT

Página 78

10-1REFRIGERATION DIAGRAMSSM DNGDCI 2-E.1 GB10. REFRIGERATION DIAGRAMS10.1 Heat Pump Models10.1.1 DNG 50/60/72/80 Cooling mode Heating modeEEVEEVEEVEE

Página 79

11-1TUBING CONNECTIONSDATA BOOK - DNG DCI11. TUBING CONNECTIONS TUBE (Inch)TORQUE (Nm)¼” ⅜” ½” ⅝” ¾”Flare Nuts15-18 40-45 60-65 70-75 80-85Valve

Página 80 - 12.9.13 Jumper Settings

12-1CONTROL SYSTEMSM DNGDCI 2-E.1 GB12 CONTROL SYSTEM12.1 General Functions and Operating RulesThe DCI software is fully parametric.All the model dep

Página 81

12-2CONTROL SYSTEMSM DNGDCI 2-E.1 GB12.1.2 Target Frequency Setting12.1.2.1 Target Frequency Setting for DCI 50/60The compressor target frequency i

Página 82 - Test Mode

12-3CONTROL SYSTEMSM DNGDCI 2-E.1 GBOAT ODUCodeH ODUCodeC IDU NLOAD≤ -5 3 3 Refer to sect.1.12..1≥ -5 3.8 312.1.3 Frequency Changes ControlWhen the u

Página 83 - SW Parameters

12-4CONTROL SYSTEMSM DNGDCI 2-E.1 GB12.1.5 Minimum On and Off Time 3 minutes12.1.6 Indoor Fan Control8 Indoor fan speeds are determined for each mode

Página 84

12-5CONTROL SYSTEMSM DNGDCI 2-E.1 GBCompressorTarget FrequencyOFAN SpeedRoutinARoutinBRoutinCRoutinDFreq=0 OFF OFF OFF OFF10 = Freq < OFLowFreq Low

Página 85

12-6CONTROL SYSTEMSM DNGDCI 2-E.1 GB12.1.8.2 EEV Control for DCI72/80The target EEV value is the sum of open loop value (OL) and a result of the accu

Página 86 - 13. TROUBLESHOOTING

1-4INTRODUCTIONSM DNGDCI 2-E.1 GB1.11 Matching Table1.11.1 R410AOUTDOOR UNITSINDOOR UNITSMODELREFRIGER.DNG 50 DCI DNG 60 DCI DNG 72 DCI DNG 80 DCI

Página 87

12-7CONTROL SYSTEMSM DNGDCI 2-E.1 GB12.2 Fan ModeIn high/ medium/ low indoor fan user setting, unit will operate fan in selected speed.In AutoFan user

Página 88

12-8CONTROL SYSTEMSM DNGDCI 2-E.1 GB12.7 Auto Cool/Heat ModeWhen in auto cool heat mode unit will automatically select between cool and heat mode acco

Página 89

12-9CONTROL SYSTEMSM DNGDCI 2-E.1 GB12.9.2 Indoor Coil Overheating Protection12.9.2.1 Indoor Coil Overheating Protection For DNG60ICTICT TrendFas

Página 90

12-10CONTROL SYSTEMSM DNGDCI 2-E.1 GB12.9.3.2 Compressor Overheating Protection for DCI 72/80CTTCTT TrendFast DecreasingDecreasingNoChangeIncreasingF

Página 91 - 13.1.6 Judgment by MegaTool

12-11CONTROL SYSTEMSM DNGDCI 2-E.1 GB12.9.5.2 Heat Sink Overheating Protection For DCI72/80HSTDelta HST<-2 -2 -1,0,1 2 >2HST ≥ 81 SC SC SC SC S

Página 92

12-12CONTROL SYSTEMSM DNGDCI 2-E.1 GBOCT – Outdoor Coil TemperatureOAT – Outdoor Air TemperatureTLD – Time from Last DeicingDI – Deicing Interval (Tim

Página 93

12-13CONTROL SYSTEMSM DNGDCI 2-E.1 GB12.9.7.2 Outdoor coil Deicing Protection For DCI72/80Entering Deicing ConditionsDeicing operation will start whe

Página 94

12-14CONTROL SYSTEMSM DNGDCI 2-E.1 GB12.9.8 Condensate Water Over Flow ProtectionEach of the pins P1, P2, P3 can have two options:1 – When it is shor

Página 95

12-15CONTROL SYSTEMSM DNGDCI 2-E.1 GB12.9.9 Indoor Unit Dry ContactIndoor unit Dry contact has two alternative functions that are selected by J9.Jump

Página 96

12-16CONTROL SYSTEMSM DNGDCI 2-E.1 GB12.9.11 On Unit Controls and Indicators12.9.11.1 Indoor Unit Indicatiors for All Models Except for Floor/Ceilin

Página 97

2-1PRODUCT DATA SHEETSM DNGDCI 2-E.1 GB2. PRODUCT DATA SHEET2.1 DNG50 DCI Model Indoor Unit DNG 50 DCIModel Outdoor Unit DCI 50 R410AInstallation Met

Página 98

12-17CONTROL SYSTEMSM DNGDCI 2-E.1 GB12.9.13 Jumper Settings12.9.13.1 Indoor Unit Controller0 = Open Jumper (disconnect jumper).1 = Close Jumper (

Página 99

12-18CONTROL SYSTEMSM DNGDCI 2-E.1 GB12.9.14 Outdoor Unit Controller12.9.14.1 Outdoor Unit Controller For DCI60JP9 Jumper Layout:Reserved (PIN 9) ODU

Página 100 - SM DNGDCI 2-E.1 GB

12-19CONTROL SYSTEMSM DNGDCI 2-E.1 GB12.10 Test Mode12.10.1 Entering Test ModeSystem can enter Test mode in two ways:Automatically when the following

Página 101

12-20CONTROL SYSTEMSM DNGDCI 2-E.1 GB12.11 SW Parameters12.11.1 Indoor Units SW ParametersModel dependent parameters - DNGUnitA(DNG50)B(DNG60)C(DNG

Página 102

12-21CONTROL SYSTEMSM DNGDCI 2-E.1 GB12.11.2 Outdoor Units SW Parameters:Model dependent parameters for DCI50/60# Name Single DCI-50 Single DCI 60 1

Página 103

12-22CONTROL SYSTEMSM DNGDCI 2-E.1 GB12.11.3 Model dependent parameters for DCI72/80Compressor Parameters ValueMinOFFTime 3MinOnTime 3MaxCTT1 90MaxCT

Página 104

13-1TROUBLESHOOTINGSM DNGDCI 2-E.1 GB13. TROUBLESHOOTING 13.1 Troubleshooting for DNG50/60 DCIWARNING!!!When Power Up – the whole outdoor unit contro

Página 105 - 14.3 Indoor Unit: DNG 72 DCI

13-2TROUBLESHOOTING SM DNGDCI 2-E.1 GB No Symptom Probable Cause Corrective Action 9Unit works in wrong mode (cool instead of heat or heat instead o

Página 106 - 14.4 Indoor Unit: DNG 80 DCI

13-3TROUBLESHOOTINGSM DNGDCI 2-E.1 GB13.1.3 Judgment by Indoor/Outdoor Unit DiagnosticsEnter diagnostics mode - press for five seconds Mode button in

Página 107 - 14.9 Outdoor Unit: DCI 50

13-4TROUBLESHOOTING SM DNGDCI 2-E.1 GB 13.1.4 Indoor Unit DiagnosticsNo Problem 5 4 3 2 11 RT-1 is disconnected 0 0 0 0 12 RT-1 is shorted 0 0 0 1 03

Página 108 - 14.10 Outdoor Unit: DCI 50

2-2PRODUCT DATA SHEETSM DNGDCI 2-E.1 GB2.2 DNG60 DCI Model Indoor Unit DNG 60 DCIModel Outdoor Unit DCI 60 R410AInstallation Method of Pipe FlaredChar

Página 109 - 14.5 Outdoor Unit: DCI 60

13-5TROUBLESHOOTINGSM DNGDCI 2-E.1 GB13.1.5 Outdoor Unit DiagnositsNo Problem 5 4 3 2 11 OCT is disconnected 0 0 0 0 12 OCT is shorted 0 0 0 1 03 CTT

Página 110 - 14.6 Outdoor Unit: DCI 60

13-6TROUBLESHOOTING SM DNGDCI 2-E.1 GB 13.1.6 Judgment by MegaToolMegaTool is a special tool to monitor the system states. Using MegaTool requires: A

Página 111 - 14.7 Outdoor Unit: DCI 72/80

13-7TROUBLESHOOTINGSM DNGDCI 2-E.1 GB13.1.8 Precaution, Advise and Notice Items13.1.8.1 High voltage in Outdoor unit controller. Whole controller, i

Página 112 - 14.8 Outdoor Unit: DCI 72/80

13-8TROUBLESHOOTING SM DNGDCI 2-E.1 GB 13.2 Troubleshooting for DNG72/80 DCIWARNING!!!When Power Up – the whole outdoor unit controller, including th

Página 113

13-9TROUBLESHOOTINGSM DNGDCI 2-E.1 GBNo Symptom Probable Cause Corrective Action 7One indoor unit or more are operating in cool mode with no capacit

Página 114

13-10TROUBLESHOOTING SM DNGDCI 2-E.1 GB No Symptom Probable Cause Corrective Action 19The unit stop suddenly during operationEMC interference to the

Página 115

13-11TROUBLESHOOTINGSM DNGDCI 2-E.1 GBNo Problem 543211OCT bad 000012CTT bad 000103HST bad 000114OAT bad 001005OMT bad 001016RGT bad 001107 OFAN/Compr

Página 116

13-12TROUBLESHOOTING SM DNGDCI 2-E.1 GB 13.2.3.2 Outdoor fault corrective actionsNo Fault Name Probable Cause Corrective Action1 OCT badThermistor n

Página 117

13-13TROUBLESHOOTINGSM DNGDCI 2-E.1 GBNo Fault Name Probable Cause Corrective Action18 No communication A No signals in line A Check communication19C

Página 118 - APPENDIX A

13-14TROUBLESHOOTING SM DNGDCI 2-E.1 GB 13.2.4 Fault Code for Indoor unitPressing Mode button for long will activate diagnostic mode by the acknowled