PERFORMANCE DATA & PRESSURE CURVES
5-3
SM SAFRPM 1-A.0 GB
5.2 SAF045 / OU10-47T R410A
5.2.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OD Coil(
o
C)
Data
ENTERING AIR WB/DB ID Coil(
o
C)
15/21 17/24 19/27 21/29 23/32
15
(1)
TC
12.96 13.43 13.74 14.07 14.28
SC
9.22 9.61 9.98 10.23 10.42
PI
3.11 3.11 3.12 3.12 3.14
20
(1)
TC
12.54 13.22 13.64 13.96 14.26
SC
9.03 9.52 9.92 10.21 10.39
PI
3.37 3.38 3.39 3.41 3.42
25
TC
11.87 12.81 13.47 13.88 14.22
SC
8.80 9.34 9.85 10.13 10.32
PI
3.64 3.67 3.69 3.72 3.74
30
TC
11.10 12.08 13.05 13.52 13.92
SC
8.52 9.06 9.63 9.91 10.10
PI
3.93 3.99
4.02
4.05 4.09
35
TC
10.28 11.15
12.30
12.92 13.53
SC
8.10 8.69 9.41 9.68 9.87
PI
4.24 4.31
4.38
4.41 4.44
40
TC
9.34 10.17
11.10
12.14 12.76
SC
7.64 8.22 8.90 9.18 9.37
PI
4.57 4.64 4.72 4.78 4.83
46
TC
8.11 8.86 9.75 10.77 11.60
SC
7.04 7.54 8.12 8.40 8.59
PI
5.00 5.07 5.19 5.26 5.32
LEGEND
TC – Total Cooling Capacity, kW
SC – Sensible Capacity, kW
PI – Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OD – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, Optional Accessories are needed.
Comentários a estes Manuais