PRODUCT DATA SHEET
2-3
SM SAFRPM 1-A.0 GB
2.3 SAF045 / GC 45 R22
Model Indoor Unit SAF045
Model Outdoor Unit GC 45
Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
(4)
Btu/hr 43670 43670 52540
kW 12.80 12.80 15.40
Power input
(4)
kW 4.56 4.56 5.12
EER (Cooling) or COP(Heating)
(4)
W/W 2.81 2.81 3.01
Energy efficiency class C C D
Power supply
V 400
Ph 3
Hz 50
Rated current A 8.1 8.1 9.1
Power factor 0.85 0.85 0.85
Prated (IDU) W 160
Prated (IDU+ODU) W 6500
Starting current A 65.8
Circuit breaker rating A 3X20
INDOOR
Fan type & quantity Centrifugal x 1
Fan speeds H/M/L RPM 550/480/380
Air flow
(1)
H/M/L m3/hr 1700/1500/1188
External static pressure Min Pa 0
Sound power level
(2)
H/M/L dB(A) 64/62/60
Sound pressure level
(3)
H/M/L dB(A) 54/52/50
Moisture removal l/hr 4.5
Condenstate drain tube I.D mm 25
Dimensions WxHxD mm 540x1776x415
Net Weight kg 52
Package dimensions WxHxD mm 632x1893x535
Packaged weight kg 60
Units per pallet units 6
Stacking height units 2 levels
OUTDOOR
Refrigerant control Capillary tube
Compressor type,model Scroll,Dakin JT160BCBY1L
Fan type & quantity Propeller(direct)x 2
Fan speeds H RPM 780
Air flow H m3/hr 4680
Sound power level H dB(A) 64
Sound pressure level
(3)
H dB(A) 56
Dimensions WxHxD mm 950x1260x412
Net Weight kg 120
Package dimensions WxHxD mm 1100x1300x470
Packaged weight kg 150
Units per pallet Units 1
Stacking height units 1
Refrigerant type R22
Standard charge kg(7.5m) 3.1kg
Additional charge
4m < Length < 7.5m: +0g; 7.5m < Length <
25m: +500g; 25m < Length < 38m: +980g;
38m<Length<50m: +1580g;
Connections between
units
Liquid line In.(mm) 3/8"(9.53)
Suction line In.(mm) 3/4"(19.05)
Max.tubing length m. Max.50
Max.height
difference
m. Max.20
Operation control type Remote control
Heating elements (Option) kW 2.1
Others
(1)
Airflow in ducted units;at nominal external static pressure.
(2)
Sound power in ducted units is measured at air discharge.
(3)
Sound pressure level measured at 1-meter distance from unit.
(4)
Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
(5)
The declared value’s tolerance is in accordance with Eurovent.