PRODUCT DATA SHEET
2-8 SM SX Ser1-A.3 GB
2.8 SX 24 / OU7-24T R410A
Model Indoor Unit SX-24
Model Outdoor Unit OU7-24T
Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
(1)
Btu/hr 23300 23300 24000
kW 6.83 6.83 7.03
Power input
(1)
kW 2.27 2.27 2.13
EER (Cooling) or COP(Heating)
(1)
W/W 3.01 3.01 3.03
Energy efficiency class B B C
Power supply V/Ph/Hz 400/3/50
Rated current A 3x7 3x7 3x7
Starting current A 55
Circuit breaker rating A 3x16
INDOOR
Fan type & quantity Centrifugal x 2
Fan speeds H/M/L RPM 1200/980/840
Air flow
(2)
H/M/L m3/hr 1000/900/780
External static pressure Min-Max Pa 0
Sound power level
(3)
H/M/L dB(A) 64/62/59
Sound pressure level
(4)
H/M/L dB(A) 53/51/48
Moisture removal l/hr 2.7
Condensate drain tube I.D mm 16
Dimensions WxHxD mm 1200x630x190
Weight kg 33
Package dimensions WxHxD mm 1270x710x280
Packaged weight kg 38
Units per pallet units 7
Stacking height units 7 levels
OUTDOOR
Refrigerant control Capillary tube +Restrictor
Compressor type ,model Rotary, Mitsubishi NN27VBAMT
Fan type & quantity Propeller(direct) x 1
Fan speeds H/L RPM 850
Air flow H/L m3/hr 3100
Sound power level H/L dB(A) 67
Sound pressure level
(4)
H/L dB(A) 58
Dimensions WxHxD mm 900x680x340
Weight kg 74
Package dimensions WxHxD mm 985x730x406
Packaged weight kg 77
Units per pallet Units 6
Stacking height units 2 levels
Refrigerant type R410A
Refrigerant chargless distance kg/m 2.16kg/12.5m
Additional charge per 1 meter g/m
12.5m<Add 430g<25m
25m<Add 530g<30m
Connections between
units
Liquid line In.(mm) 3/8"(9.53)
Suction line In.(mm) 5/8"(15.88)
Max .tubing length m. Max.30
Max .height difference m. Max.15
Operation control type Remote control
Heating elements kW
Others All Season kit factory option
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.