CONTROL SYSTEM
11-22 SM SX Ser1-A.3 GB
DRY
(RT - SPT) [
o
c]
+2
+1
0
-1
-2
ON
OFF
ON
OFF
LOW
OFF
DRY-ON
DRY-OFF
ON
OFF
Time [min]
10
20
30
40 50
Max 15 minutes
3.5
min
Note1
6 min
Note 2
C
OMP
OFAN
HE1
&
HE2
IFAN
RV
Max 15 minutes
5 minutes COMP
ON time
NOTES
1. When DRY is ON, the COMP is forced OFF for 3.5 min (longer
than the 3 min Min COMP- OFF time) after every 15 min of
continuous COMP operation.
2. When DRY is OFF, the COMP is forced ON for 6 min (longer
than the 3 min Min COMP- ON time) after every 15 min of
continuous COMP OFF time.
3. When DRY is changed from ON to OFF or vice versa, the
limits mentioned in (1) & (2) are ignored. The COMP operation
is only controlled by the 3 min Min OFF time and 1 min Min
ON time.
4. In DRY Mode, IFAN is LOW when COMP is ON, and is OFF
when COMP is OFF.
5. HEs are always OFF in DRY Mode.